Motor control centre · MCC

MCC panels

One lineup that starts, stops and protects the motors in your plant. An MCC groups motor starter feeders on a common busbar, with local and remote control, status indication and interfaces to your PLC or SCADA.

Busbar rating
Up to 4000 A
Fault level
Up to 50 kA, 1 s
Starters
DOL, SD, soft, VFD
Modules
Fixed or drawout

Overview

We design each MCC around your motor list. Every feeder is sized for its motor's kW rating and starting method, with Type 2 coordination between the breaker, contactor and overload relay so a fault on one motor doesn't damage the starter.

Modules can be fixed, plug-in or fully drawout. Drawout MCCs let you pull out a faulty starter and replace it with a spare in minutes without shutting down the rest of the board, which matters on process lines that can't stop.

Technical specifications

MCC panels: standard specifications. Ratings and makes are finalised to your requirement.
Rated operational voltage415 V AC, 3-phase 4-wire, 50 Hz
Control voltage230 V AC or 24/110 V DC
Main busbar currentUp to 4000 A
Short-time withstand currentUp to 50 kA for 1 s
IncomerACB or MCCB, with metering and protection
Starter typesDOL, star-delta, soft starter and VFD feeders
CoordinationType 2 between MCCB/MPCB, contactor and overload relay
Module constructionFixed, plug-in or drawout with service, test and isolated positions
Motor protectionThermal or electronic overload relays; motor protection relays on large drives
Control and indicationLocal/remote selector, start/stop push buttons, run/trip/off lamps, ammeter per feeder
Form of separationForm 3b or Form 4b
EnclosureCRCA sheet steel, 2 mm structure and 1.6 mm doors and covers
Degree of protectionIP42 or IP54, indoor
FinishPowder coat, RAL 7035 or your shade
StandardsIS 8623; starters to IEC 60947-4-1

What's inside

  • ACB or MCCB incomer with metering
  • Horizontal main busbar and vertical droppers to each module
  • Starter modules with MCCB or MPCB, contactors and overload relays
  • Soft starter and VFD sections with forced ventilation
  • Control terminals and interposing relays for PLC/SCADA
  • Spare modules and space for future feeders

Applications

  • Pumping stations and water treatment
  • Cement, steel and chemical plants
  • Food, pharma and packaging lines
  • HVAC plant rooms and chillers
  • Conveyors and material handling
  • Compressor houses

Options

  • Intelligent MCC with Modbus/Profibus feeders
  • Motor protection relays with thermal models
  • Harmonic filters and line reactors for VFDs
  • Remote I/O and hard-wired PLC interface
  • Space heaters and anti-condensation
  • Spare drawout modules

Built and tested in-house

We cut, bend, weld and powder-coat the enclosures in our own workshop, then assemble and wire every panel to drawings you approve before fabrication starts. Before dispatch each panel goes through high-voltage, insulation resistance and functional tests, and your team is welcome to witness them.

See how we build, from drawing to commissioning

Frequently asked questions

When should I choose a drawout MCC over a fixed one?

Choose drawout when downtime is expensive. A faulty module can be withdrawn and a spare plugged in without switching off the rest of the MCC. Fixed MCCs cost less and suit plants where planned shutdowns are acceptable.

What is Type 2 coordination?

Under IEC 60947-4-1, Type 2 coordination means that after a short circuit the starter is still fit for further use, apart from possible light welding of contactor contacts. It limits damage and repair time on each feeder.

Can VFDs and soft starters go in the same MCC?

Yes. We place drives in dedicated sections with ventilation sized for their losses, and add line reactors or filters where harmonics need to be controlled.

Do you wire the MCC to our PLC?

We bring start, stop, run, trip and remote/local signals to terminals marked for your PLC, or provide communication-enabled feeders on Modbus or Profibus.